Technical Specifications
Performance
|
Specifications
|
Acceptable liquids |
Water and water like liquids. (cooling, well, waste, pure, drinking, heating and tap water) This product is NOT compatible with flammable, corrosive or toxic liquids. |
Max. Operating pressure |
(for lifetime) 12 bar(a) at +40°C
(for lifetime) 6 bar(a) at +85°C
|
Max. Test pressure |
18 bar(a) at +40°C |
Operating temperature |
<+85°C |
Ambient temperature |
-20 .. +50°C |
Accuracy at >=50%FS |
<2%RD |
Accuracy at <50%FS |
<1%FS |
Rangeability |
Up to 1:20 |
Approvals
|
Specifications
|
Drinking water approval |
KTW / W270 |
EMC |
EN 61326-2-3 |
Mechanical
|
Specifications
|
Materials (wetted parts) - Sensor paddle - Body - Seals |
ETFE PA6T/6l (40% GF) EPDM |
Ingress protection (housing) |
IP65 |
Process connection |
G11/4 |
Electrical
|
Specifications
|
Output |
4..20mA |
Power supply |
10..33Vdc |
Load |
<(Uin-10V) / 20mA |
Connection type |
M12 x 1 |
Pressure Drop