Technical Specifications
Performance
|
Specifications
|
Accuracy* |
± 1%RD |
Repeatability |
1% |
Rangeability |
1:20
|
Signal output starting from
|
~ 0.25 l/min
|
Medium |
Water and other conductive liquids with a minimum conductivity of 20 μS/cm (lower conductivity affects the accuracy) |
Medium temperature
|
-10...60 °C (not freezing) |
Operating pressure
|
10 bar(a) (20 °C), 8 bar(a) (40 °C), 6 bar(a) (60 °C)
|
Nominal diameter
|
DN 8
|
Process connection
|
G½'' BSP male thread |
Flow indication
|
Green LED: flow proportional flashing;
|
Response time
|
< 100 ms |
Mechanical
|
Specifications
|
Materials (wetted parts) |
Housing: ABS Electrodes: Stainless Steel 316L Process connections: PVDF Measuring pipe: PVDF Grounding rings: Stainless Steel 316L
|
Protection |
IP65 |
Electrical
|
Specifications
|
Frequency output
|
|
Pulse rate
|
1000 pulses/l |
Resolution
|
1.00 ml/pulse |
Signal shape
|
Square wave signal, duty cycle 50:50 (Push-Pull)
|
Signal current
|
<100 mA |
Electrical connection
|
4-pin-plug M12x1
|
Power supply
|
12..24 VDC±10% |
Power consumption
|
Max 3.6 W
|
Electrical protection measures
|
short-circuit proof, protected against polarity reversal
|
Pin assignment
|
 |
PIN 1: +U PIN 2: Analog output PIN 3: GND PIN 4: Frequency output
|
|
* test conditions: Water 23 °C
Pressure Drop

Electrical connection
The MAG-VIEW™ has an Push-Pull frequency signal and analog output that corresponds to flow rate [l/min].