                    MVM-030-PA
Low-Flow Magnetic Inductive Flow meters for water-like liquids
- Pulse and Analog output (4..20 mA)
 - Compact, weatherproof (IP65) design
 - No moving parts (no mechanical wear)
 - Interference free operation
 - Independence to inlet/outlet pipework
 - Fast response
 - Free pipe cross section: low ΔP, insensitive to contamination
 
Water like liquids
        Frequency and Analog 4..20mA
        Flow ranges
This magnetic flow meter is suitable to measure flows of water and other conductive liquids within a flow range of 0.1 .. 30 lpm.
| Model | Min | Max | output signal starts | 
|---|---|---|---|
| MVM-030-PA | 0.1 l/min | 30 l/min | ~ 0.1 l/min | 
Scope of delivery
- Magnetic Flow Meter
 - Calibration certificate
 - Packing box
 - MAG-VIEW Manual
 - (optional) instrument cable
 
Features of MVM-030-PA Magnetic Flow Meter
- Makes liquid flows visible by
- Blinking LED (red/green)
 
 - Frequency output and Analog output (4..20 mA)
 - No mechanical wear
 - No moving parts
 - Ease of mounting and operation
 - Mounting in any position
 - Free pipe cross section
 - No additional pressure drop
 - Fast response (<500 ms)
 - Insensitive with contaminated liquids
 - Ideal solution for interference free operation combined with a long-life cycle
 - Can be used in areas where flow sensors with moving parts cannot be applied
 - Wide independence to the inlet and outlet pipe creates the advantage to be able to install in compact machines with cramped confines
 
Technical specifications
Measurement / control system
Flow range 
                
                    
                    0.1..
                    30
                    l/min
                    
                
            Accuracy
                
                    
                    
                    
                    
                    ±0.7 % of reading ±0.3 % of range
                
            Reproducibility
                
                    
                    
                    
                    
                    1%
                
            Pressure rating (PN)
                
                    
                    
                    
                    
                    PN16
                
            Nominal diameter
                
                    
                    
                    
                    
                    DN 7
                
            Flow / alarm indication
                
                    
                    
                    
                    
                    Green LED: flow proportional flashing
                
            Signal output starting from
                
                    ~
                    
                    0.1
                    l/min
                    
                
            Medium
                
                    
                    
                    
                    
                    Water and other conductive liquids
(minimum conductivity of 50 μS/cm)
            (minimum conductivity of 50 μS/cm)
Medium Temperature
                
                    
                    -20...
                    90
                    °C
                    
                
            Rangeability
                
                    
                    
                    
                    
                    1:300
                
            Response time (sensor)
                
                    
                    
                    
                    
                    < 500 ms
                
            Mechanical parts
Material (wetted parts)
                
                    
                    
                    
                    
                    Housing: Aluminium pressure diecasted
Electrodes: Stainless Steel 1.4571
Process connections: Stainless Steel 1.4571
Measuring pipe: PEEK-GF30
Gasket: EPDM
            Electrodes: Stainless Steel 1.4571
Process connections: Stainless Steel 1.4571
Measuring pipe: PEEK-GF30
Gasket: EPDM
Process connections
                
                    
                    
                    
                    
                    G1/2'' BSP male thread
                
            Ingress protection
                
                    
                    
                    
                    
                    IP65 and IP67 with MFO.CB.25
                
            Electrical properties
Power supply
                
                    
                    12...
                    24
                    Vdc
                    ±10%
                
            Max. power consumption
                
                    
                    
                    
                    
                    max. 150 mA
                
            Analog output
                
                    
                    
                    
                    
                    4..20 mA, Signal current corresponds to flow rate of 0…30 l/min
                
            Frequency output
                
                    
                    
                    
                    
                    Pulse rate / K-factor : 1000 pulses/l
Resolution : 1,0 ml/pulse
Signal shape : Push-Pull
            Resolution : 1,0 ml/pulse
Signal shape : Push-Pull
Signal shape
                
                    
                    
                    
                    
                    Square wave signal, pulse duty ratio 50:50, Push-Pull
                
            Signal current
                
                    
                    
                    
                    
                    max. 100 mA, current limited
                
            Pin assignment
                
                    
                    
                    
                    
                    PIN 1: +UB
PIN 2: analog output 4..20mA
PIN 3: GND
PIN 4: frequency output
PIN 5: do not connect
            PIN 2: analog output 4..20mA
PIN 3: GND
PIN 4: frequency output
PIN 5: do not connect
Electrical connection
                
                    
                    
                    
                    
                    5-pin-plug M12x1
                
            Downloads
Declaration of Conformity
Stepfile
Applications
The fields of application for this magnetic flow meter are diverse:
- Can be used in areas where flow sensors with moving parts (paddle wheel, turbine sensors) cannot be applied due to contaminated media
 - Sensor is intended for continuously measuring of flow rates or for dosing / batching of electrically conductive liquids with a minimum of 50µS/cm
 - Water distribution
 - Chemical feed
 
Frequently Asked Questions
- Can the MAG-VIEW QA-series be used with low viscosity mineral slurries?
 - Is the MAG-VIEW sensitive to air bubbles?
 - MAG-VIEW export codes (TARIC, HS, ECCN and Country of origin)
 - The fluid conductivity changes during the measurements, is that a problem?
 - Can the MAG-VIEW be used with demineralized – deionized water?
 